CALIBRATION OF MAGNETOSTRICTIVE LEVEL TRANSMITTER :

Today we will be talking about calibration of the magnetostrictive level transmitter.


In my old article, I have a cover-up a detailed explanation about the magnetostrictive transmitter. Link is attached below,


Now let's dig into our article.


(source: GOOGLE)


Nowadays all the transmitter are a SMART type comes with an easy keypad interface, calibration of this type of transmitter is a matter of pressing keypad and you all done with calibration.


Follow the below step for the successful calibration,


1. For LRV keep tank level at 0% level which equals 4mA output. Use your manual to enter in calibration mode. Now by observing level at 0% hit the keypad to set output at 4 mA.


2. For URV set level of the tank at 100% which is equal to 20 mA. By observing level is perfectly at 100% use your keypad to set output at 20 mA.


3. Check output at 25%, 50% and 75% too.


4. Repeat the above step for better accuracy.